*Table 1 Program
01: 10 Execution Interval (seconds)
1: Panel Temperature (P17)
1: 1 Loc [ RefTemp ]
2: Thermocouple Temp (DIFF) (P14)
1: 1 Reps
2: 11 10 mV, Fast Range
3: 5 DIFF Channel
4: 1 Type T (Copper-Constantan)
5: 1 Ref Temp (Deg. C) Loc [ RefTemp ]
6: 2 Loc [ TempDegC ]
7: 1.0 Mult
8: 0 Offset
3: If time is (P92)
1: 0 Minutes (Seconds --) into a
2: 1 Interval (same units as above)
3: 10 Set Output Flag High (Flag 0)
4: Real Time (P77)
1: 1220 Year,Day,Hour/Minute (midnight = 2400)
5: Average (P71)
1: 1 Reps
2: 2 Loc [ TempDegC ]
6: If (X<=>F) (P89)
1: 2 X Loc [ TempDegC ]
2: 4 <
3: 31 F
4: 11 Set Flag 1 High
7: If (X<=>F) (P89)
1: 2 X Loc [ TempDegC ]
2: 3 >=
3: 32 F
4: 21 Set Flag 1 Low
;*********Cell Transceiver Control Segment***********
;Include this segment only if a cell transceiver is
;used and controlled by the CR23X. Segment enables
;transceiver for 10 minutes, at the top of each hour,
;during routine operation, but turns cell phone on
;immediately if an alarm condition occurs.