CS450/CS455 Pressure Transducer
Periodic evaluation of the desiccant is vital for keeping the vent tube dry. The
CS450/CS455 ships with the desiccant tube attached. To assess the
effectiveness of the desiccant, use one of the following:
The desiccant in the tube changes color from blue to pink when the drying
power is lost.
An enclosure humidity indicator such as CSI pn 28878 Humidity Indicator
Card.
7.1 Every Visit
Collect data.
Visually inspect wiring and physical conditions.
Check indicating desiccant or enclosure humidity indicator; service if
necessary.
Check battery condition (inspect physical appearance and use a keyboard
display, PDA, or laptop to view the battery voltage).
Check all sensor readings; adjust transducer offsets if necessary.
Check recent data.
7.2 Every Two to Three Years or on a Rotating Schedule
Send the CS450/CS455 in for inspection and have it serviced and/or
replaced as needed.
8. Troubleshooting
The most common causes for erroneous pressure-transducer data include:
poor sensor connections to the datalogger
damaged cables
damaged transducers
moisture in the vent tube
Problem:
Unit will not respond when attempting serial communications.
Suggestion:
Check the power (Red is +V and Black is Ground) and signal (White is SDI-12
Data) lines to ensure proper connection to the datalogger. Check the datalogger
program to ensure that the same port the SDI-12 data line is connected to is
specified in the measurement instruction.