
IRGASON Integrated CO
2
/H
2
O Open-Path Gas Analyzer and 3D Sonic Anemometer
Remove the wicks during the winter. The wicks will accumulate snow or
freezing rain, resulting in blockage of the sonic signals.
When installing wicks, be sure they are located in the proper position. The top
wick must be flush with the transducer face, with the wick tail located at the
lowest point of the transducer (see Figure 9-1). The end of the bottom
transducer wick must extend above the transducer face by one-half to one mesh
line (see Figure 9-1). Secure the wicks to the transducer with a drop of
adhesive (e.g., super glue). Take care that super glue is not deposited on the
transducer face.
Replacement top wicks (p/n 17388) and bottom wicks (p/n 17389) can be
purchased from Campbell Scientific. A complete set of wicks consists of three
top wicks and three bottom wicks.
FIGURE 9-1. Proper location of the sonic top wick (left)
and bottom wick (right)
9.2.2 Gas Analyzer Wicks
IRGASON gas analyzer windows are polished and slanted at an angle to
prevent water from collecting on their surfaces. However, due to increased
surface tension at the interface with the snout, water can pool at the edges and
partially block the optical path and attenuate the signal. To minimize the
occurrence of such events and the resulting data loss, consider using wicks.
The weave of the wick fabric promotes capillary action that wicks the water
away from the edge of the windows. The seam and the straight edge of the
wicks are permeated with a rubberized compound to prevent them from
shifting during operation.
Proper installation of the wicks is critical. They should not block or encroach
on the optical path. Before installation, record signal strengths for both H
2
O
and CO
2
. Following installation, these values should be unchanged.
26
Comentários a estes Manuais