Campbell RF400 Manual Página 70

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 69
Appendix D. Setting Up RF401-to-CR206(X) Communications
RF401 #1 Setup for Example 2 (see Figure D-7)
1. Since RF401 #1 will connect to a PC, select AutoSense or RS-232 Active
Interface.
2. Choose PakBus Aware for the Protocol.
3. Use 9600 k baud rate to communicate with the CR206. The baud rate
setting in the LoggerNet Setup screen must also be set to 9600.
4. Select Hop Sequence 0, which matches the CR206(X)'s hop sequence.
5. Select Net Address 0, which matches the CR206(X)'s address.
6. The Radio Address is fixed at 0 when the Protocol is "PakBus Aware".
7. Select <2ma - 1 Sec Header for the Power Mode.
8. Select Retry Level Low.
9. Entry of a PakBus Address is disabled in DevConfig for the "PakBus
Aware" protocol.
FIGURE D-7. DevConfig Deployment panel showing the RF401#1
setup for Example 2.
D-8
Vista de página 69
1 2 ... 65 66 67 68 69 70 71 72 73 74 75 ... 125 126

Comentários a estes Manuais

Sem comentários