TD ADDENDUM—OVERVIEW
AD-OV-7
The program to make the measurements and send the desired data to Final Storage has been
enter
ed. The program is complete. The clock must now be set so that the date and time tags
are correct. (Here the example reverts back to the key by key format.)
Key Display Explanation
*5 00:21:32 Enter *5 Mode. Clock running but not set correctly.
A 05:01.01 Advance to month-day (MMDD).
1004 05:1004 Key in MMDD (Oct 4 in this example).
A 05:1990 Enter and advance to location for year.
1994 05:1994 Key in year.
A 05:00:21 Enter and advance to location for hours and minutes
(
24 hr. time).
1324 05:1324 Key in hrs.:min. (1:24 PM in this example).
A 05:27.250 Key in seconds
30 05:30
A 13:24:30 Clock set and running. Changes made when A was
pr
essed.
*0 LOG 1 Exit *5, compile Table 1, commence logging data.
OV5.3 EDITING AN EXISTING PROGRAM
When editing an existing program in the
CR10X
, entering a new instruction inserts the
instruction; entering a new parameter replaces
the previous value.
To insert an instruction, enter the program table
and advanc
e to the position where the
instruction is to be inserted (i.e., P in the data
portion of the display) key in the instruction
number, and then key A. The new instruction
will be inserted at that point in the table,
advance through and enter the parameters.
The instruction that was at that point and all
instructions following it will be pushed down to
follow the inserted instruction.
An instruction is deleted by advancing to the
ins
truction number (P in display) and keying #D
(Table 4.2-1).
To change the value entered for a parameter,
advanc
e to the parameter and key in the correct
value then press A. Note that the new value is
not entered until A is keyed.
OV6. DATA RETRIEVAL OPTIONS
Data is retrieved over some form of
telecommunications link, whether it be RF
(radio), telephone, short haul modem, coaxial
cable (mulitdrop) , or direct link. The table data
operating system does not support on-line
output to peripheral storage devices (see Figure
OV 6.1-1).
The retrieval of data does NOT erase those
data f
rom the Data Storage Tables in Final
Storage. The data remains in the table ring
memory until:
The are written over by new records of data.
(
Section 2.1)
Input Storage memory is reallocated
(
Section 1.5)
The datalogger program is changed and
c
ompiled.
Power to the datalogger is turned off.