Section 14. PakBus Networking
14-2
Starting with LoggerNet, the configurations of the devices in the example
network are as follows:
Example Network – LoggerNet Configuration
Setup Description
Device Map Map CR800_10 as a router to CR800_20:
Note: CR800_10 discovers CR800_20 by neighbor filter so that
LoggerNet can communicate with CR800_20 through CR800_10.
PakBusAddresses LoggerNet PakBusPort address defaults to 4094.
Assign unique PakBus addresses to PakBus devices in device map:
CR800_10
CR800_20
Beaconing Disable LoggerNet beaconing (on PakBusPort) so it can’t discover
CR800_20 directly.
Baud Rate Set PakBusPort baud rate the same as the communication peripheral used
(base RF401’s RS-232 port):
Example Network – CR800_10 Configuration (Router)
Setup Description
General If CR800 settings have changed from factory defaults, use the Device
Configuration Utility to set Factory Defaults. Then proceed with setups
shown below.
PakBus Address Using Device Configuration Utility, Deployment, make CR800’s PBA the
same as in LoggerNet map (be sure to Apply the setting):