RAWS-H Remote Automated Weather Station
matter; either lead can be connected to either terminal. The CH100
charger/regulator has two functions: 1) blocks any current flow from the
battery to the solar panel, and 2) limits the source current to the battery.
5.1.3 Troubleshooting, Solar Panel
If a problem with the solar panel is suspected, the solar panel may be checked
by measuring the voltage output from the solar panel. Check the voltage with a
voltmeter connected between the two leads going to the CH100
charger/regulator “CHG” “CHG” terminals located inside the environmental
enclosure (15 VDC to 28 VDC). There must be solar radiation incident on the
panel and there must be a load connected to the solar panel. The load can be
the datalogger, other equipment, or a 75 ohm resistor capable of dissipating
solar panel power between the two leads. No voltage output implies a bad
solar panel, regulator, or cable. The magnitude of the voltage output depends
on the incident solar radiation. Check the sensor cable. Disconnect the
connector and look for damaged pins.
5.2 Charger/Regulator
5.2.1 General Description, 12 V Charger/Regulator (part #CH100)
The 12 volt charger/regulator (part #CH100) is a charging regulator for 12 V
rechargeable batteries. The CH100 is connected to an external charging source
such as an unregulated solar panel (part # SP20-Handar or SP10-Handar) or a
wall charger (part #9591-Handar). The CH100 charger/regulator has two
functions: 1) blocks any current flow from the battery to the solar panel, and 2)
limits the source current to the battery.
FIGURE 5.2-1. 12 volt charger/regulator
5.2.2 Wiring, 12 V Charger/Regulator (part #CH100)
The leads from the RAWS connector panel “BATT CHARGER/SOLAR
PANEL” connector COLOR CODED PURPLE are wired to the CH100
“CHG” terminals. Polarity does not matter; either lead can be connected to
either terminal. The charge indicating diode should be “ON” when voltage to
the charging circuitry (CHG Terminals) is present.
An internal and/or external battery can be connected to the CH100
Charger/Regulator by means of the INT (Internal) or EXT (External)
7