CR510 OVERVIEW
OV-15
Instruction # Parameter
(Loc.:Entry) (
Par.#:Entry) Description
07: P73 Maximize instruction
01:1 One repetition
02:10 Output time of daily maximum in hours and minutes
03:2 Data source is Input Storage Location 1.
08: P74 Minimize instruction
01:1 One repetition
02:10 Output the time of the daily minimum in hours
and minutes
03:1 Data source is Input Storage Location 1.
The program to make the measurements and to send the desired data to Final Storage has
been entered. At this point, Instruction 96 is entered to enable data transfer from Final Storage
to Storage Module.
09:P96 Activate Serial Data Output.
1:71 Output Final Storage data to Storage Module.
OV5.3 SETTING THE DATALOGGER TIME
The next example shows how to set the datalogger date and time using the CR10KD. Here the
example reverts back to the key-by-key format.
Key Display
Explanation
5
00:21:32 Enter 5 Mode. Clock running but perhaps not set correctly.
A
05:0000 Advance to location for year.
1
9
9
8
05:1998 Key in year (1998).
A
05:0000 Enter and advance to location for Julian day.
1
9
7
05:197 Key in Julian day.
A
05:0021 Enter and advance to location for hours and minutes (24 hr. time).
1
3
2
4
05:1324 Key in hrs.:min. (1:24 PM in this example).
A
:13:24:01 Clock set and running.
0
LOG 1 Exit 5, compile Table 1, commence logging data.