Appendix A. Single-Ended Measurements
A-7
Example A-4. Measuring Single Ended Thermocouples with the Input Location Indexed and
no Step Loop Index
01: Beginning of Loop (P87)
1: 0 Delay
2: 6Loop Count
02: Thermocouple Temp (SE) (P13)
1: 2 Reps
2: 21 2.5 mV 60 Hz Rejection Range
3: 1 SE Channel
4: 1 Type T (Copper-Constantan)
5: 1 Ref Temp (Deg. C) Loc [ RefTemp ]
6: 18-- Loc [ TC_1 ]
7: 1.0 Mult
8: 0.0 Offset
03: End (P95)
Example A-5. Measuring Single Ended Thermocouples with the Input Location Indexed and
Step Loop Index
01: Beginning of Loop (P87)
1: 0 Delay
2: 6 Loop Count
02: Step Loop Index (P90)
1: 2 Step
03: Thermocouple Temp (SE) (P13)
1: 2 Reps
2: 21 2.5 mV 60 Hz Rejection Range
3: 1 SE Channel
4: 1 Type T (Copper-Constantan)
5: 1 Ref Temp (Deg. C) Loc [ RefTemp ]
6: 18-- Loc [ TC_1 ]
7: 1.0 Mult
8: 0.0 Offset
04: End (P95)