9522B & COM9522B Iridium Data Modem
16
Figure 18. Generic - Modem Configuration
5.1.5 Step 5: PakBusPort Configuration
As in Figure 19, be sure the Communications Enabled box is checked, change the
Maximum Baud Rate to 19200 (9600 for a CR10X), set the Beacon Interval to all
zeros, add 15 seconds of Extra Response Time and if present add a 200 ms delay
under Delay Hangup.
You may change other settings in this configuration to suit your particular
application. It is recommended to also use a Maximum Time On-line as part of your
configuration. Once complete move to Step 6 in order to configure the datalogger.