Campbell 21X Manual do Operador Página 69

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 191
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 68
SECTION
7.
MEASUREMENT
PROGRAMMING
EXAMPLES
The fixed
100
ohm
resistor must
be thermally
stable.
lts
precision
is not
important
because
the
exact resistance
is incorporated,
along with
that
of the PRT,
into the calibrated
multiplier.
The 10
ppm/oO
temperature
coefficient
of
the
fixed
resistor will
limit the error
due
to its change
in
resistance
with
temperature
to
less
than
0.1soO
over
the
-10
to 40oC
temperature
range.
Because
the measurement is
ratiometric
(Rs/Rf),
the
properties
of the 1O kohm resistor
do not
affect
the result.
As
in the
example
in
Section 7.9,
the excitation
voltage is
calculated to be
the maximum
possible,
yet
allow
the +50mV
measurement
range.
The
10
kohm resistor
has
a
tolerance
of
t1%;thus,
the
lowest
resistance
to
expect from
it is
9.9
kohms. We
calculate
the maximum
excitation voltage
(V*)
to keep
the
voltage
drop
across
the
PRT less
than 50mV:
0.050V >
Vx
115.54/(9900+115.54);
V" .
4.
The
excitation
voltage
used is 4.3V.
The
multiplier used in Instruction
7 is
in
the same
manner
as in
Section 7.9.
In
this
example, the
multiplier
(R/Ro)
is
assumed to
100.93.
The
3
wire
half
bridge
compensates
for
lead wi
resistance
by
assuming
that the resistance of
wire A
is the
same
as the resistance of wire B.
The maximum difference
expected in
wire
resistance
is
2o/o, but is more
likely to be on the
order
of
1"/". The resistance
of R. calculated
with Instruction 7, is
actually R,
plus
the
difference in
resistance
of wires A
and
B. The
average resistance of 22 AWG wire
is
16.5
ohms
per
1000 feet, which would
give
each 500
foot lead
wire
a nominal
resistance of 8.3 ohms.
Two
percent
of 8.3
ohms is 0.17 ohms.
Assuming
that
the
greater
resistance
is in wire
the resistance measured for
the PRT
(Ro
=
100
ohms) in
the ice
bath would be
100.17
ohms, and
the
resistance
at
40oC
would be
115.71.
The
measured
ratio R./Ro
is
1.1551;
the
actual ratio
is 115.54/100
=
1.1554. The
temperature computed
by Instruction
16
from
the measured ratio would
be about
0.1oC
lower
than the actual temperature
of the PRT.
This
source
of error
does not
exist in the example in
Section 7.9, where
a
4 wire
half bridge
is
used
measure
PRT
resistance.
The
advantages of the
3
wire
half bridge are
it
only requires 3 lead wires
going
to
the sensor
and
takes 2 single- ended input
channels,
whereas
the
4 wire half
bridge requires 4 wires
and 2
ditferential channels.
01:
01:
02:
03:
o4:
05:
06:
07:
08:
09:
02:
P16
01:
1
02: 1
03: 2
04:
1
05: 0
P9
1
3
3
1
1
4200
1
PROGRAM
Full BR w/Compensation
Rep
50 mV
slow EX Range
50 mV
slow BR
Range
lN
Chan
Excite
all reps
w/EXchan 1
mV Excitation
Loc
[:Rs/R0
I
1.0111 Mult
0 Offset
Temperature
RTD
Rep
R/Ro Loc Rs/RO
Loc
[:TEMP
degC]
Mult
Offset
7.10 1OO
OHM PRT
IN
3
WIRE
HALF
BRIDGE
The temperature
measurement requirements
in
this
example
are the same as in
Section 7.9. In
this case,
a three wire
half
bridge, Instruction 7,
is
used
to measure
the
resistance
of
the PRT.
The
diagram
of the PRT circuit is
shown in
Figure
7.10-1.
EX]
21X
Ht 1
LOI
+
Rp
10K
OHM
1%
TEIVPERATURE
COEFFICIENT
<
25
5OO,LEAD LENGTH,
,, O*'(
6
PPM/'c
RS
100 oHM
PRT
FIGURE
7.10-1.
3 Wire Half Bridge
Used to
Measure
100 ohm PRT
7-6
Vista de página 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 190 191

Comentários a estes Manuais

Sem comentários