SECTION
9. INPUT/OUTPUT
INSTRUCTIONS
TABLE 9-1. Input
Voltage
Ranges
and
Codes
Range Code
Slow
Fast
16.67ms
250ps
Integ.
Integ.
FullScale Range
Resolution
1
2
3
4
11
12
13
14
t5
millivolts
+15
millivolts
t50
millivolts
t500
millivolts
t5000
millivolts
0.33
microvolts
1. microvolts
3.33
microvolts
33.3
microvolts
333.
microvolts
5t*
15*"
'
Differential measurement;
resolution for single-ended
measurement
is
twice
value shown.
**
The lhtegration times
for
ranges
5 and
15 are
1.67ms
and
251ts
respectively.
: When a
voltage
input
exceeds
the
range
programmed,
the
value which is
is set to the
maximum negative
number
and displayed
as
-99999
in high
or
-6999
in low
resolution.
01:
02:
03:
***
1 SINGLE.ENDED
VOLTS
**'
FUNCTION
This
instruction is used
to
measure
voltage
at
a
single-
endep
input with
respect to
ground.
Standard
O(ttput
(multiplier
=
1, offset
=
0)
is in
millivolts.
PARAM.
DATA
NUMBER WPE
DESCRIPTION
2 Repetitions
2 Range
code
2 Channel
number for first
measuremenl
4
Input
location
for first
measuremenl
FP Multiplier
FP
Offset
Input
locatidns altered:
1
per
measurement
***
2
DIFFERENTIAL
VOLTS
*'*
FUNCTION
This
instruclion
reads the
voltage
difference
between
thQ
high
and
low
inputs of
a
differential
channel.
T4ble 9-1 contains
allvalid voltage
ranges
and
ltheir
codes.
Both the
high
and
low
inputs
mustlbe within
tSV
of
the 21X's
ground
(see
Commpn
Mode Range
in
Section 13.2).
Pyranometer and thermopile
sensors
require a
jumper
between
LOW and GROUND
to
keep
them in Common
Mode Range. Standard
Output
(multiplier
=1,
offset
=0)
is
in millivolts.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
Repetitions
Range code
Channel
number
lor
first
measurement
Input location
for first
measurement
Multiplier
Offset
Input
locations
altered:
1
per
measurernent
***
3 PULSE COUNT
*"*
There
are
three
pulse
input
types
which
may be
measured with the
Pulse
Count
Instruction.
HIGH FREQUENCY
PULSE
In this
configuration,
the minimum
detectable
pulse
width
is
2 microseconds
i.e. the
maximum
frequency is 250
kHz
with
a 5Oo/o
duty cycle.
The 8 bit counter
has a
maximum
input
frequency
of
2550
Hz and
the
16 bit option
a
maximum of 250
kHz.
2
2
2
4
FP
FP
01:
02:
03:
o4:
05:
06:
04..
05:
06:
9-1