PakBus Networking Guide
5
d. Configure Standby Mode to “< 24 mA always on”
e. In Standard Setup configure the Active Interface = Datalogger CSDC (by
default this will be CSDC 7).
f. Save All Parameters and Exit Setup.
Step 3 – Establish Temporary Direct Communications to
CR10XPB_1
a. Connect CR10XPB to 12 VDC power supply and turn on 12V power.
b. Using an SC12 cable and SC32B, connect the CR10XPB to the LoggerNet
PC’s active COM port.
c. Attach CR10KD keyboard display to CR10XPB using SC12 cable.
d. In LoggerNet Setup, configure this device map (and apply it).
(leave all settings defaults)
e. In the LoggerNet Setup device map make the PakBus Address for
CR10XPB_1 = 1.
f. Set the CR10XPB’s PakBus Address = 1 as follows:
Press *D15 on keyboard/display.
Key “0001” into window 15: and press *0 to save the new setting.
Disregard for now the other windows of *D15.
Step 4 – Write CR10XPB Program
a. Open Edlog in LoggerNet, start a new CR10X-TD program, key in the
following (TD programs are used in TD and PB dataloggers). This
program will serve as a vehicle for carrying the PakBus Address and
router settings to CR10XPB_1. The program also illustrates that, although
functioning as a router, the datalogger can still perform all standard
datalogger functions such as taking measurements and storing data.
*Table 1 Program
01: 1 Execution Interval (seconds)
1: Batt Voltage (P10)
1: 1 Loc [ Battery ]
2: Internal Temperature (P17)
1: 2 Loc [ Panel_Temp ]