Appendix C. NL100 TcpServer to RF400-Router to 20 CR205s Network
C-2
NL100 Configuration Menu Settings
(Any NL100 options not shown above are disabled).
A PakBus Address is required by setup even though not used.
RF400 Settings
In a PakBus rf network all radios must have the same radio and network
addresses and hopping sequence setting. Addressing is accomplished using the
unique PakBus addresses assigned to the PakBus devices (dataloggers).
1. Configure RF400 radio with the same Radio Address, Net Address, and
Hopping Sequence as the CR205s. If there will be no other RF400s in the
area, you can use default settings, otherwise choose some random settings
and configure all alike.
2. RF400 connected to NL100
Active Interface = “AutoSense”
Standby Mode = “< 24 mA always on”
3. RF400 connected to CR510
Active Interface = CSDC (7 by default but could be 8)
Standby Mode = < 24 mA always on
CR205 Settings
1. Configure all CR205s with the same Radio Address, Net Address, and
Hopping Sequence using the same settings as the RF400 has.
2. Configure each CR205 with a unique PakBus address (“Datalogger
Address” in PakCom) starting with “1” and ending with “20.”