PakBus Networking Guide
67
Remedy 3
Set all network radios exactly the same in the above parameters. Network
RF400s’ Active Interfaces may vary from node to node, however, they will
typically be configured for CSDC 7 or 8 except for a ‘base’ radio which is
typically AutoSense or M.E.. Dataloggers automatically detect the RF400’s
port (Active Interface) for packet communications, however, the potential
neighbor hello port or beacon port must be configured to match the RF400’s
Active Interface, or no discovery of neighbors will take place.
Possible reason 4
A CR200 Series has just received an OS download resetting network address,
radio address, hopping sequence, and radio power mode to defaults.
Remedy 4
Configure CR205 settings to agree with network.
Possible reason 5
The two routers in the path to the CR205 have neighbor filters and at least one
of the neighbor filters doesn't list the other as a potential neighbor.
Remedy 5
If you have two in-range routers using neighbor filters, in order for them to
discover one another you must list each of them as a potential neighbor in the
other’s neighbor filter.
8.3 Can’t LoggerNet communicate with datalogger-router in
network?
(PC-RF400~~~RF400-CR10XPB~~~CR205)
Possible reason
The datalogger-router has more than one M.E. peripheral cabled to it.
Remedy
Connect only one M.E. device to a datalogger (or change one M.E. peripheral
to CSDC 8 port).
8.4 Changed P190 port type and it no longer communicates
with remote.
Possible reason
The Active Interface of the communications device (for example, RF400
Series) no longer matches the P190 port.
Remedy
Make the communications device Active Interface agree with P190 Parameter
1.