PakBus Networking Guide
43
The master’s P193 automatically handles clock synchronization with the P196
remote.
6.1.7 P197 – Force Route through Address
Purpose:
To enter a PakBus Address into a datalogger’s routing table forcing the first
hop where user wants to avoid using the auto-routing broadcast.
Example:
7: PakBus - Force Route (P197)
1: 17 Local DL Port
2: 0005 Neighbor (Address of first hop)
3: 0010 Destination PakBus Address (same as neighbor if only one hop)
4: 01 Hops to Destination Node
6.1.8 P198 – Set Setting
Purpose:
Program control instruction to configure the Port Setting in a PakBus
datalogger. A P63 or P68 should follow with the value for the changed setting.
If the line 2 Address is the PakBus Address of the datalogger itself, P198 can
change its own setting.
Example:
8: PakBus - Set Setting (P198)
1: 17 SDC 7
2: 0012 Address
3: 3 Result Code Loc [ Result ]
9: Extended Parameters (P63)
1: 02 Option
2: 00 Option
3: 00 Option
4: 00 Option
5: 00 Option
6: 00 Option
7: 00 Option
8: 00 Option
Changes PakBus Address 12 port from 17 (CSDC 7) to 2 (ME, 9600 baud)