C-1
Appendix C. NL100 TcpServer to
RF400-Router to 20 CR205s Network
In this configuration LoggerNet does 60 minute scheduled collections from
remote CR205s via NL100 configured as TcpServer and an RF400 for
communications. In this configuration, the CR205s have to be relatively close
to the NL100. The network configuration described in Appendix B shows how
to extend range with a ‘repeater’/router.
Notice that the LoggerNet, NL100, RF400 and CR205 setups are the same as
in Appendix B. The difference is the router which is missing. This
demonstrates the fact that adding a router is transparent to LoggerNet. Adding
a router only involves configuring the router’s port (CSDC 7, CSDC 8, or
Modem Enabled) and configuring the way the datalogger/router will discover
its neighbors (beacons or potential neighbors) and you are done.
Hardware Setup
PC----(LAN)----NL100
(RS232)
----
(RS232)
RF400~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~CR205_1
~~~~CR205_2
~~~~CR205_3
LoggerNet Device Map
IPPort
PakBusPort (
CR200_1 (PakBus Address = 1)
CR200_2 (PakBus Address = 2)
CR200_3 (PakBus Address = 3)
(PakBus Address = n)
In the PakBusPort screen configure beaconing for 0 seconds. LoggerNet will
find the CR510PB as a static route from its device map. The first time you
connect, PakBusGraph will show the CR510PB and all the CR205s which are
neighbors to the CR510PB.
LoggerNet Schedule Tab
Collection Interval – 60 minutes
Primary Retry Intervals – 20 minutes
Number of Primary Retries – 2
Secondary Retry Interval – 240 minutes