PakBus Networking Guide
66
Possible reason 3
No PakBusPort in device map between root and datalogger.
Remedy 3
Add PakBusPort.
Possible reason 4
No PakBus OS in datalogger
Remedy 4
If you have two in-range routers using neighbor filters, in order for them to
discover one another you must list each of them as a potential neighbor in the
other’s neighbor filter.
8.2 LoggerNet can’t communicate via datalogger-router to a
certain remote datalogger.
(PC-RF400~~~RF400-CR10XPB~~~RF400-CR510~~~CR205)
Possible reason 1
A datalogger router has insufficient *D15 max nodes, max neighbors, or max
routers configured.
Remedy 1
Increase the *D15 numbers.
*D15 settings of 000x, 6, 6, 6, 0 are reasonable for a router in a network of
under a half dozen nodes (see *D15 Set PakBus Address and Routing Table,
Section 4.1.2.1).
*D15 settings allocate memory similar to *A. It is a good
idea, when configuring *D15 settings, to leave ‘room to
grow.’
Changing *D15 settings later on could result in loss of data
as *0 is entered to compile new settings.
Possible reason 2
Last datalogger router has no means configured of discovering the remote
datalogger.
Remedy 2
Configure the datalogger router with either a neighbor filter or a beacon. Make
sure Neighbor Filter potential neighbors include the remote datalogger’s
address. Whether you set up a beacon or Neighbor Filter make sure the port so
configured matches the communications device port configuration. For
example, if the selected neighbor filter port is “17”, make sure that the RF400
Active Interface is “CSDC 7.”
Possible reason 3
An RF400 Series radio is set to a different Hopping Sequence, Network
Address, Radio Address, or Standby Mode.